Components

Earth leakage circuit breaker 1P+N, 16A, C-characteristic, 30mA

Earth leakage circuit breaker 1P+N, 16A, C-characteristic, 30mA
  • AT90222
  • 8712259536590
  • Suitable for expansion in Click-mate NXT distribution boards.
  • Component width: 36 mm.
ETIM article class: Earth leakage circuit breaker
Rated voltage
230 V
Rated current
16 A
Rated fault current
0.03 A
Rated insulation voltage Ui
264 V
Rated impulse withstand voltage Uimp
4 kV
Leakage current type
A
Surge current capacity
1 kA
Voltage type
AC
With interlocking device
Yes
Frequency
50 Hz
Degree of protection (IP)
IP20
Width in number of modular spacings
2
Built-in depth
70 mm
Ambient temperature during operating
-25 - 55 °C
Pollution degree
2
Release characteristic
C
Connectable conductor cross section multi-wired
0.75 - 35 mm²
Number of poles (total)
2
Connectable conductor cross section solid-core
0.75 - 35 mm²
Number of protected poles
1
Current limiting class
3
Flush-mounted installation
No
Concurrently switching neutral conductor
Yes
Over voltage category
3
Rated short-circuit breaking capacity according to EN 61009
6 kA
Rated short-circuit breaking capacity according to IEC 60947-2
15 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Disconnection characteristic
Undelayed
Anti-nuisance tripping version
Yes
Additional technical data (ETIM)
Product information

Components

With the Click-mate NXT you can easily put together your custom distribution boxes. You choose one of the cabinets from the basic range based on the space available in the meter cabinet or the required components. You can then add, remove or move specific components. For example, it is possible to place components that are subject to a long-term load, such as groups for PV installations or charging stations, 'freely'. Or to reserve free space for components for home automation or energy management systems.

Download
Product data sheet

Earth leakage circuit breaker 1P+N, 16A,...

Article no: AT90222

Download